Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 REV. G 061502
ALARMS
Message IndicationLogRelayPhoneHorn
Rectifier Under Voltage 1 No 1 HA Service Required
Rectifier Under Voltage OK Off No 1 HA Condition Cleared
SBM Bypass Failed 1 4 1 HA Service Required
SBM Bypass Failed OK Off No 1 HA Condition Cleared
Scheduled UPS Off Active 1 No 1 HA User Action Required
Scheduled UPS Off Inactive 1 No 1 HA User Action Required
Scheduled UPS Off/On Active 1 No 1 HA User Action Required
Scheduled UPS Off/On Inactive 1 No 1 HA User Action Required
Scheduled UPS On Active 1 No 1 HA User Action Required
Scheduled UPS On Inactive 1 No 1 HA User Action Required
Selective Trip 1 No 1 A Service Required
Selective Trip OK Off No 1 A Condition Cleared
Shutdown Imminent 1 No 1 HA User Action Required
Shutdown Imminent Clear Off No 1 HA Condition Cleared
UPS Tripped 1 4 1 A User Action Required
Warning: Battery Time is Low 1 No 1 HA User Action Required
Warning: Battery Time is Low OK Off No 1 HA Condition Cleared
Table Ke y To L o g Column
HA --- Event recorded in History and Active Logs.
A --- Event recorded in Active Log only.